1.1 Introduction
The HZRC5000A Power Quality Analyzer is a high-precision professional instrument developed for power grid quality testing and analysis, complying with IEC 61000-4-30 Class A. It is equipped with a 7-inch capacitive color touch screen for easy and responsive operation, bilingual (Chinese/English) interface, and IP65-rated enclosure.
This instrument can simultaneously measure 4 voltage channels (Phase A/B/C and neutral-to-ground voltage) and 4 current channels (Phase A/B/C and neutral current). It supports comprehensive measurements including voltage/current peak values, maximum/minimum values, three-phase unbalance factor, short-term & long-term voltage flicker, transformer K-factor, active/reactive/apparent power, power factor, displacement power factor, active/reactive/apparent energy, voltage/current harmonics, interharmonics and total harmonic distortion (THD). Real-time voltage/current waveforms, phasor diagrams and harmonic bar graphs are available for display.
It monitors transient voltage/current anomalies and faults with waveform recording capability. The instrument adopts a high-speed dual DSP + ARM multi-core architecture, delivering high-speed data acquisition and processing. It supports 512 samples per cycle gapless waveform recording with a maximum continuous recording duration of 10 minutes. The system automatically captures and records full waveforms during voltage sag, voltage interruption, voltage swell and current transient events, facilitating rapid fault diagnosis. The built-in screenshot function saves real-time screen content for later review.
Also known as a smart three-phase power quality analyzer or multi-functional power tester, this device integrates the functions of a harmonic analyzer, phase volt-ampere meter and electrical parameter tester. It is widely applied in power utilities, petrochemical, metallurgy, railway, industrial enterprises, research institutions and metrology departments for comprehensive analysis and diagnosis of voltage, current, power, energy, harmonics and phase parameters.
1.2 Functional Parameters
Function | Measured & Displayed Parameters |
Parameter Overview | DC,THD,DF,CF,KF values of voltage and current for each phase A, B, C,N;voltage deviation,frequency deviation |
Waveform | Real-time waveformm of Phase A/B/C/N voltage and urrent . |
Harmonics | THD,fundamental,2nd~50th harmonics,0th~49th interharmonics of voltage and current . |
Max/Min | RMS maximum,RMS minimum,real-time RMS,positive peak and negative peak of Phase A/B/C/N voltage and current. |
Power Energy | Three-phase and total active power(P),reactive power(Q),apparent power(S),power factor(PF),active energy,reactive energy,apparent energy. |
Vector graphic | Three-phase (A/B/C)vector,phase angle,three-phase unbalance factor and frequency. |
Unbalance | Voltage/current unbalance,positive-sequence,negative sequence and zero sequence components . |
Flicker | PST and PLT. |
Screenshot | Capture and save current screen;up to 800 screenshots can be stored . |
Logger | All test parameters can be selected, automatically recorded, and trend charts can be generated for display. Storage situation: Each record can select all 223 parameters, and can be recorded for 5 days at an interval of 1 second; it can be recorded for 300 days at an interval of 1 minute; the fastest setting can be set Record once every 0.2 seconds. The instrument can store a total of 100 records. |
Transient
| Capture transient events of voltage and current, including voltage sag, voltage swell, voltage interruption, voltage transient, and current transient. Storage condition: It can monitor faults for an extended period and store the voltage data from 55-66 cycles before and after the occurrence of a fault event. The current waveform, also known as fault recording, can store 2000 sets of such fault voltage and current waveform in a single fault recording. The instrument can store up to 100 sets. The secondary monitoring system can store up to 200,000 sets of fault waveforms in total. |
Monitor | Monitor RMS voltage, THD, PST, unbalance factor, frequency and operational status of power parameters . |
Waveform Recording | Waveform recording, fully capturing 512 data points within each cycle waveform, ensuring no subtle voltage or current changes are missed. Storage status: The device has a total of 8 channels for voltage and current, with 512 points per cycle. It can record continuously without gaps for 10 minutes in one recording session, and the instrument can store up to 20 recording sessions. |
1.3 General Specifications
Power Supply | Rechargeable lithium battery:7. 4V,7000mAh, backup charger. |
Battery Indicator | Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute. |
Battery Runtime | The battery can work continuously for about 6 hours when fully charged. |
Display mode | 7 - inch capacitive color touch screen . |
Size of Clamp | 008 Clamp: Φ8mm; 040 clamp: Φ40mm; 240F Flexible Coil: Φ240mm . |
Instrument dimensions | 274mm×225mm×113mm (L × W × H) . |
Channels | 4U/4I |
Phase Voltage Range | 0. 10V~1000V . |
Line Voltage Range | 0. 20V~2000V . |
Current Range | 008Clamp:10mA~10. 0A; 040Clamp:0.10A~200A; 240F Flexible Coil:1.0A~10.00KA |
Frequency | 40Hz~70Hz . |
Standard Class | IEC 61000-4-30 Class A. |
Language | Chinese,English. |
Communication | USB . |
Auto Power-off | No auto power-off during logging, monitoring, transient capture or waveform recording . |
Auto power-off with prompt after 10 minutes of inactivity in other modes | |
Backlight | Support (for dim environments and night use) . |
Length of voltage test leads | 2m . |
Length of current sensor leads | 2m . |
Working temperature and humidity | -10°C~40°C; below 80%Rh. |
Storage temperature and humidity | -10°C~60°C; below 70%Rh. |
Input Impedance (Voltage) | > 1MΩ . |
Withstand Voltage | 3700V AC (50Hz) for 1 minute between internal circuit and enclosure . |
Insulation Resistance | ≥ 10MΩ between internal circuit and enclosure. |
Enclosure Rating | IP65 . |
Safety Compliance | IEC 61010:1000V CAT III/600V CAT IV;IEC61010-031,IEC61326;Pollution Degree 2. |